Power transformerS9 series oil-immersed power transformer of class 35kV with dual-winding off-circuit-tap-changing
  • Product overview
  • Apply
  • Specifications
  • Technical
It is applicable for power systems of AC50Hz and rated working voltage 35kV, used as transformation equipment for substations of 35kV.

Iron
The iron core is made of cold-rolled grain-oriented silicon steel sheets with high magnetic conductivity, with inclined joint laminated structure. Section of the core limbs is of multi-class ladder round, with uniform section with that of yoke. 

Winding 
The winding adopts corrugated oil duct with non-dipping process, bound by shrinkable tape; all windings are of concentric coils; taps of HV winding with corresponding tapping voltage shall be led to the tap switch, and the switch shall be installed on the box cover. Power supply must be cut off first when changing the tapping voltage.

Installation of protection device 
●Transformers of all capacity specifications have been equipped with pressure relief valve; 
●Gas relay with alarm and tripping terminals is available on request. 

Oil-temperature measurement device 
●All the transformers are equipped with tube holder for glass-stem thermometer that is set on the top of oil tank, and immersed in oil for about 120±10mm;
●1000~2000kVA transformer is equipped with outdoor signal thermometer;

Transformer oil tank 
●Transformer oil tank is composed of corrugated walls with powder painted surface and reinforced with film. Corrugated cooling fin not only has cooling function, but also has “breathing” function, the elasticity of corrugated cooling fin make it adapt to the change of oil volume due to change of temperature. So this hermetically sealed transformer does not have oil conservator, which decreases the height of transformer. 
●The transformer adopts vacuum oil-injection technology during encapsulation that thoroughly removes the moisture from transformer, and keeps the transformer oil from contacting the air. This technology also avoid insulation performance reduction or oil aging due to entering of oxygen or moisture, it improves operation reliability of transformer. 
● Installation height: altitude shall not exceed 1000m
● Ambient temperature: -40℃~40℃
Rated capacity Installation dimension(mm)
kVA L W H C1 C2
800 2140 1320 2120 820 820
1000 2400 1330 2170 820 820
1250 2470 1350 2190 820 820
1600 2550 1375 2250 820 820
2000 2700 1400 2300 1070 1070
2500 2520 2300 2365 1070 1070
3150 2600 2350 2410 1070 1070
4000 2680 2560 2490 1070 1070
5000 2730 2750 2550 1070 1070
6300 2960 2800 3080 1475 1475
8000 3170 2610 3210 1475 1475
10000 3250 3220 3400 1475 1475
12500 3370 3260 3540 1475 1475
16000 3470 3280 3580 1475 1475
20000 3950 3450 3850 1475 1475
25000 4570 3800 3900 1475 1475
31500 5000 4150 4000 1475 1475

S9-800 ~ 31500/35 transformers
Rated capacity Voltage combination Connection group Loss (KW) No-load current  Short-circuit impedance Weight (kg)
kVA HV kV High-voltage tapping range LV kV  symbol No-load On-load % % Oil weight Gross weight
800 35
38.5
±5%
±2×2.5%
3.15
6.3
10.5
Yd11 1.23 9.90 1.0 6.5 790 3040
1000 1.44 12.15 1.0 850 3410
1250 1.76 14.67 0.9 950 3890
1600 2.12 17.55 0.8 1060 4620
2000 2.72 19.35 0.7 1195 5345
2500 3.20 20.70 0.6 1285 5960
3150 3.80 24.30 0.56 7 1470 6695
4000 4.52 28.80 0.56 1760 8350
5000 5.40 33.03 0.48 1850 9400
6300 6.56 36.90 0.48 7.5 2200 11300
8000 YNd11 9.00 40.50 0.42 2450 13240
10000 10.88 47.70 0.42 3230 16600
12500 12.60 56.70 0.40 8 3585 19400
16000 15.20 69.30 0.40 4420 23100
20000 18.00 83.70 0.40 6060 29700
25000 21.28 99.00 0.32 6490 38200
31500 25.28 118.80 0.32 6890 40300

Order guide

Please specify the product model, rated capacity, HV/LV rated voltage and high-voltage tapping range, phase number, frequency, connection group symbol and so on in the order.